電(dian)纜(lan)豎井用于弱電(dian)還是供(gong)電(dian)電(dian)纜(lan)?
電纜豎(shu)井中應(ying)分層(ceng)設置(),電纜溝每隔必定的間隔(60米)應(ying)采納防火阻隔辦法。
電纜(lan)豎井中應分(fen)層設置(),電纜(lan)溝(gou)每隔(ge)必定的間隔(ge)(60米(mi))應采納防火阻隔(ge)辦法。
A. 防火隔板
B. 防火門
C. 防火袋
D. 滅火器
電(dian)纜豎井歸于(yu)弱電(dian)仍是(shi)強電(dian)?
電(dian)(dian)(dian)(dian)纜豎井是高層建筑(zhu)物用(yong)于筆(bi)直(zhi)走供電(dian)(dian)(dian)(dian)電(dian)(dian)(dian)(dian)纜或通(tong)訊電(dian)(dian)(dian)(dian)纜的(de)筆(bi)直(zhi)通(tong)道,和(he)電(dian)(dian)(dian)(dian)梯豎井相似。一般的(de)電(dian)(dian)(dian)(dian)纜豎井里(li)強電(dian)(dian)(dian)(dian)和(he)弱(ruo)電(dian)(dian)(dian)(dian)都(dou)有,但強電(dian)(dian)(dian)(dian)和(he)弱(ruo)電(dian)(dian)(dian)(dian)一般分(fen)隔敷設。
電氣(qi)豎井(jing)內所用的電纜(lan)橋架,標準型號要契合規劃要求,選用鍍鋅(xin)制(zhi)品,鍍鋅(xin)鋼板的厚度在橋架寬度小(xiao)于(yu)(yu)400mm時,厚度不小(xiao)于(yu)(yu)1.5mm;在400~800mm之間時,厚度不小(xiao)于(yu)(yu)2mm;大于(yu)(yu)800mm時,厚度不小(xiao)于(yu)(yu)2.5mm。
電纜橋架應平直,無顯著歪曲,支架應焊接結實,無明顯變形,下料差錯應在5mm范圍內,切斷應無卷邊毛刺。
防火堵料(防火枕)、防火涂料應選用經國家判定的定型產品。
豎井內的配電箱應有出廠合格證、出產許可證、“CCC”認證標志和認證證書復印件及實驗記載。
電線、電纜及附件應選用契合國家現行技術標準的產品,并應有出廠合格證、“CCC”認證標志和認證證書復印件。電線、電纜橋架還應有出產許可證,契合電纜橋架的標準挑選。
電氣豎井中運用的輔助資料:鉆頭、電焊條、氧氣、乙炔氣、調合漆、焊錫、焊劑、橡膠絕緣帶、塑料絕緣帶、黑膠布等。
金屬膨脹螺栓:依據答應拉力和剪力及設備的裝置孔徑確認。
接線端子:依據導線截面及導線根數選用相應標準的接線端子。
電纜橋架鍍鋅資料:鋼板、圓鋼、扁鋼、角鋼、螺栓、螺母、螺絲、墊圈、繃簧墊圈等金屬資料均應選用鍍鋅制品。
|